Home » Safety Signs » Fire Extinguisher Signs » Fire Extinguisher Sign Medium Safety

Fire Extinguisher Sign Medium Safety

$14.00

Fire extinguisher location sign — medium. Photoluminescent plastic. Standard size suitable for most commercial and industrial applications.

Dispatched within 1 business dayMon–Fri
Australia-wide deliveryCalculated at cart
Quality assuredAustralian fire safety standards
(02) 8073 46279am–2pm Mon–Fri AEST

Free shipping on orders over $50!

  • Done Satisfaction Guaranteed
  • Done No Hassle Refunds
  • Done Secure Payments
GUARANTEED SAFE CHECKOUT
  • Visa Card
  • MasterCard
  • American Express
  • Discover Card
  • PayPal
SKU: SILM Categories: ,

Description

A medium-format fire extinguisher location sign in UV-rated PVC plastic. Red field with white symbol and “FIRE EXTINGUISHER” text — 225mm wide × 300mm tall. Mounted at height on the wall above the extinguisher to indicate its location to anyone approaching from any direction. The 225 × 300mm format is the standard specification for most commercial buildings, offices, warehouses, and industrial premises where a clear, conspicuous location marker is required at the mandated mounting height.

Under AS 2444:2001, every fire extinguisher installation must be accompanied by a compliant location sign. The sign’s function is to make the extinguisher visible from a distance — not just at point of reach. The medium format at 225 × 300mm provides sufficient symbol and text size to meet the visibility requirement at up to 20m, making it appropriate for most standard corridor, office, factory, and warehouse applications.

Where to Use

  • Commercial offices and corporate buildings
  • Warehouses and distribution centres — standard bays and aisles
  • Industrial facilities and workshops
  • Retail premises, showrooms, and shopping centres
  • Schools, healthcare facilities, and institutional buildings
  • Any building extinguisher installation where a medium-format sign meets the 20m visibility requirement

Key Features

  • 225mm × 300mm format — standard medium size for most commercial applications
  • UV-rated PVC plastic, 0.6mm thickness — resists fading, yellowing, and UV degradation
  • Rounded corners — no sharp edges, suitable for high-traffic areas
  • UV-rated inks — long service life without colour loss
  • Protective film — supplied with surface protection for storage and handling

Compliance & Placement

Under AS 2444:2001 clause 3.3.4, fire extinguisher location signs must be mounted at not less than 2.0m above floor level — or at the height that makes them most apparent to a person of average height approaching the extinguisher. This is a critical compliance point: the sign goes high (minimum 2m), not at the same height as the extinguisher. The extinguisher handle is mounted at maximum 1,200mm from floor level; the location sign indicating its position is mounted separately at 2m or above.

Under AS 2444:2001 clause 3.4, the sign must be clearly visible from up to 20m in all directions of approach. The 225 × 300mm format meets this requirement for most standard building configurations. At each AS 1851 service, confirm the sign is present, undamaged, securely mounted at the correct height, and clearly visible from the approach direction.

Frequently Asked Questions

How high should this sign be mounted?

AS 2444:2001 clause 3.3.4 specifies that fire extinguisher location signs must be mounted at not less than 2.0m above floor level. This is intentionally higher than the extinguisher itself — the sign is designed to be visible from a distance, marking the general location so a person can identify the extinguisher from across the room or along a corridor before they are close enough to read the cylinder label. The extinguisher handle sits at a maximum of 1,200mm; the sign indicating its location is mounted at 2m or above.

Does a sign come included when I buy a fire extinguisher?

Extinguishers are typically sold without a location sign — the sign is a separate item purchased and installed by the building owner or fire protection contractor. Under AS 2444, each extinguisher installation requires a compliant location sign. If you are purchasing extinguishers for a new installation, add the appropriate sign at the same time. The medium SILM is the standard size for most commercial applications.

What is the difference between a location sign and a type identification sign?

These are two distinct sign types serving different purposes. The location sign (this product — SILM) is mounted high (2m+) and is designed to indicate the extinguisher position from a distance of up to 20m — it is a navigational marker. A type identification sign (such as ABE, CO2, or Wet Chemical) is mounted on the wall adjacent to the extinguisher at approximately extinguisher height and identifies what type of agent the extinguisher contains. A compliant installation typically includes both: the location sign high up marking the position, and the type sign at extinguisher height identifying the agent.

Does the sign need to be visible from 20 metres?

Yes — AS 2444:2001 clause 3.4 requires that the extinguisher or its location sign must be clearly visible from a distance of up to 20m in all directions of approach. For installations in large open areas (warehouses, factory floors, car parks) where the 20m visibility requirement may be difficult to achieve with a single sign, multiple signs or a larger format sign may be required. The medium SILM is suited to standard commercial spaces where the 20m requirement can be met without additional measures.

What size sign do I need for a large warehouse or open-plan space?

For open areas, high ceilings, or locations where the sign needs to be visible at greater distances, a larger format sign may be required. Consider the SILL (large, 300 × 450mm) for high-bay warehouses, large factory floors, or locations where the sign must be readable at the full 20m approach distance. For corridors where visibility is needed in both directions, the right-angle SILS-ANGLE is the appropriate format. If you are unsure which size meets the 20m requirement for your specific location, consult your fire protection installer or building surveyor.

Additional information

Weight 0.10 kg